For details of operation by external signals, refer to [Chapter 7].
1: Operation panel, Extension panel
Press the [RUN], [STOP] key on the operation panel to run/stop the inverter.
You can do it even on the optional extension panel.
For how to set this value, refer to [4. 3].
2: Embedded Ethernet
Connect a communication cable to the Ethernet connector 1 or 2, and run/stop the inverter through
the Ethernet communication.
For details, refer to "Communication Function Instruction Manual".
3: RS485 communication (connector 1)
This has the operation panel mounted when shipped from the factory. Remove the operation panel
and connect a communication cable, and you can run/stop the inverter through the RS485
4
communication.
For details, refer to [0].
5
4: RS485 communication (connector 2)
Connect a communication cable to the RS485 communication connector 2 next to the control
terminal block. Then, you can run/stop the inverter through the RS485 communication.
For details, refer to [6. 38].
5: Communication option
Run/stop the inverter with a communication option command.
For details, refer to "Communication Function Instruction Manual".
9
Memo
5. [Fundamental operation] How to use parameters
• Assign the input terminal function "108: Terminal operation priority" to an unused input terminal.
When the input terminal is ON, run command is terminal run.
For details, refer to the table of input terminal functions in [7. 2. 1] or [11. 8].
• The priority command from the communication or terminal precedes the command set with
<CMOd: Run command select>.
5-2