• <F405: Motor rated capacity>
• <F415: Motor rated current>
• <F417: Motor rated speed>
Two parameter setting methods are provided.
1) Setting with <F400: Offline auto-tuning>
Set <F400: Offline auto-tuning> to "5".
For details, refer to [6. 23. 1].
* If an auto-tuning error occurs, set motor parameters individually by referring to [6. 23. 1]
"■Setting method 4: Manually setting motor parameter".
2) Manual setting
Set each motor constant.
For details, refer to [6. 23. 1].

6: PM motor control

4
Permanent magnet motors (PM motors) that are highly efficient can be operated in sensor-less
operation.
Setting of parameters for PM motor is required. For details, refer to [6. 23. 2].
5

7: V/f 5-point setting

V/f control characteristics can be created according to machinery. Set frequency and voltage in five
points and run the inverter with V/f control characteristics derived by connecting these points.
Set five points from VF1 to VF5 with the following parameters <F190> to <F199>.
Title
F190
F191
9
F192
F193
F194
F195
F196
F197
F198
F199
*1
100% with 200 V for 240 V class and 400 V for 480 V class.
5. [Fundamental operation] How to use parameters
Parameter name
V/f 5-point VF1 frequency
V/f 5-point VF1 voltage
V/f 5-point VF2 frequency
V/f 5-point VF2 voltage
V/f 5-point VF3 frequency
V/f 5-point VF3 voltage
V/f 5-point VF4 frequency
V/f 5-point VF4 voltage
V/f 5-point VF5 frequency
V/f 5-point VF5 voltage
Adjustment range
0.0 - FH
0.0 - 125.0
0.0 - FH
0.0 - 125.0
0.0 - FH
0.0 - 125.0
0.0 - FH
0.0 - 125.0
0.0 - FH
0.0 - 125.0
5-44
E6582062
Unit
Default setting
Hz
0.0
0.0
*1
%
Hz
0.0
*1
0.0
%
Hz
0.0
0.0
*1
%
Hz
0.0
*1
0.0
%
Hz
0.0
0.0
*1
%