Function number
Positive
Negative
logic
logic
152
153
1
154
155
156
157
158
159
162
163
164
165
170
171
172
173
176
177
200
201
9
202
203
11
11. Table of parameters
Symbol
Function
MOT2
No. 2 motor switching
PID3
External PID3 enabled
PID4
External PID4 enabled
RES2
Reset 2
External PID3 differential/
PID3R
integral reset
External PID3 plus/minus
PID3S
switching
External PID4 differential/
PID4R
integral reset
External PID4 plus/minus
PID4S
switching
PMPR
Pump control release
PWP
Parameter writing locked
PRWP
Parameter reading locked
Action
ON: No.2 motor setting + No.2 Acc/Dec + No.2 Stall (Torque
limit)
(V/f constant, <F170>, <F171>, <F172>, <F182>, <F185>,
<F500>, <F501>, <F503>)
<tHrA> (not <F182>) when <F632> = "2", "3"
OFF: No.1 motor setting + No.1 Acc/Dec + No. 1 Stall
(Torque limit)
(<Pt>, <vL>, <vLv>, <vb>, <tHrA>, <ACC>, <dEC>, <F502>,
<F601>)
ON: External PID3 enabled
ON: External PID4 enabled
ON: Reset accepted, ON -> OFF: Trip reset
ON: External PID3 differential/integral reset
ON: Plus/minus characteristics of <A340: PID control 3>
setting
OFF: Characteristics of <A340: PID control 3> setting
ON: External PID4 differential/integral reset
ON: Plus/minus characteristics of <A370: PID control 4>
setting
OFF: Characteristics of <A370: PID control 4> setting
ON: Pump release during pump control
ON: Parameter writing locked (Reading unlocked)
OFF: <F700: Parameter reading & writing access lockout>
setting
ON: Parameter reading & writing access lockout
OFF: <F700: Parameter reading & writing access lockout>
setting
11-60
E6582062
Reference
[7. 2. 1]
[6. 34. 1]
[7. 2. 1]