6. 7
6. 7. 1
<F240: Start frequency>
<F243: End frequency>
4
4
■ Function
The frequency set for <F240: Start frequency> is instantly output at startup.
This parameter is used when the delayed response of starting torque caused by the acceleration/
6
deceleration time affects the frequency.
When the output frequency is decreased to the frequency set for <F243: End frequency>, the
frequency instantly becomes 0 Hz when stopping.
■ Parameter setting
Title
9
F240
F243
■ Setting method
Use the parameters when the delayed response of starting torque caused by the acceleration/
deceleration time affects the frequency. For the setting values, 0.5-3.0 Hz (5 Hz or less) is
recommended. Overcurrent can be reduced by setting the value to the motor rated slippage or less.
Set the values so that <F240: Start frequency> is higher than <F243: End frequency>.
When <F240> is lower than <F243>, no operation is performed by any frequency command lower
than <F243>.
6. [Advanced] How to use parameters

Setting the start and end frequencies

Setting the starting frequency and the end
frequency
Parameter name
Start frequency
End frequency
Output frequency (Hz)
<F240: Start frequency>
<F243: End frequency>
0
F240 : Start frequency
Min: 0.0
X1000
Adjustment range
0.0-10.0
0.0-30.0
6-32
E6582062
STOP
0.0Hz
13:00
0.1
Hz
Max: 10.0
X100
X10
X1
Unit
Default setting
Hz
0.1
Hz
0.0
Time (s)