Standard Connection Diagram 1; Standard Connection Diagram - Sink (Negative) (Common:cc) - Toshiba TOSVERT VF-nC3E Instruction Manual

Industrial inverter (for 3-phase induction motors)
Table of Contents

Advertisement

2.2.1
This diagram shows a standard wiring of the main circuit.
2
Main circuit power supply
3ph-400V class: three-phase 380-460V
*1: VFNC3C-4004P, 4007P models don't
VFNC3E-4004P, 4007P
have the PA/+ and the PB terminals
and cannot be used with Braking
resistor.
*2: When using the OUT output terminal in
sink logic mode, short the NO and CC
terminals.
*3: When external potentiometer is connected
by using P5 terminal, set the parameter
f109=3.
*4: When VI terminal is used as a logic
input terminal, refer to page B-12.
5: Calibration is needed before using the meter.
*
Refer to section 3.3.

Standard connection diagram 1

Standard connection diagram - SINK (Negative) (common:CC)

MCCB
R/L1
S/L2
T/L3
-50/60Hz
Protective function
activation output
*5
Meter
(or 0-10V/4-20mA)
PA/+
Power
circuit
Control
circuit
FLA
VF-nC3E
VF-nC3C
FLB
FLC
Operation panel
RS485
communication
connector
*4
FM
CC
VI
+
Frequency
m eter
(am m eter)
-
External potentiometer (1k-10k)
7.5V-1mA
B-4
E6582233
Braking resistor(Option) *1
PB
U/T1
V/T2
W/T3
F
R
S1
S2
CC
P24
OUT
Ry
NO
*2
CC
P5
+
Voltage signal: 0-5V/0-10V
-
(Current signal: 4-20mA)
*3
Motor
I M
Forward run command
Reverse run command
Preset-speed command 1
Preset-speed command 2
Common
Low-speed
signal output