(4)
Protection for branch circuit
If the inverter is installed in the U.S., provide protection for the branch circuit according to
National Electrical Code and local standards.
If it is installed Canada, provide protection according to Canadian Electrical Code and local
standards.
9. 2. 3
Install a UL conformed fuse on the input side of the inverter.
For this inverter, a UL test has been conducted under the interrupting current (current that runs when
interruption of power occurs) conditions in the table below. Note that the interrupting current varies
depending on the applicable motor output.
Max input
voltage (V)
3-phase
240 V
9
3-phase
480 V
For the classes, current values, and the wire sizes of fuses, refer to the following table.
9. Measures to satisfy standards
Cautions for peripheral devices
Applicable
motor (kW)
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A
0.4 - 30
rms Symmetrical Amperes, 240 Volts Maximum When Protected by J Class
Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than
37
10,000A rms Symmetrical Amperes, 240 Volts Maximum When Protected
by J Class Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than
45 - 55
10,000A rms Symmetrical Amperes, 240 Volts Maximum When Protected
by AR Class Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A
0.4 - 30
rms Symmetrical Amperes, 480 Volts Maximum When Protected by J Class
Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than
37 - 75
10,000A rms Symmetrical Amperes, 480 Volts Maximum When Protected
by J Class Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than
90 - 110
10,000A rms Symmetrical Amperes, 480 Volts Maximum When Protected
by AR Class Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than
132
18,000A rms Symmetrical Amperes, 480 Volts Maximum When Protected
by AR Class Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than
160 - 220
18,000A rms Symmetrical Amperes, 480 Volts Maximum When Protected
by J Class Fuses
Suitable For Use On A Circuit Capable Of Delivering Not More Than
280
30,000A rms Symmetrical Amperes, 480 Volts Maximum When Protected
by T Class Fuses
Power supply short-circuit current (A)
9-8
E6582062