Toshiba TOSVERT VF-AS3 Instruction Manual page 509

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Communication
Title
Parameter name
No.
PID1 set value
F389
0389
select
Parameter for
F390
0390
manufacturer
Sleep detection
F391
0391
hysteresis
F392
0392
Wakeup deviation
F393
0393
Wakeup feedback
Parameter for
F394
0394
manufacturer
Parameter for
F399
0399
manufacturer
F400
0400
Offline auto-tuning
F401
0401
Slip frequency gain
Automatic torque
F402
0402
boost
Adjustment range
Unit
0: selected by FMOd/
F207
1: Terminal RR
2: Terminal RX
3: Terminal II
4: Terminal AI4 (option)
5: Terminal AI5 (option)
6 - 11: -
12: FPId
13,14: -
15: Terminal Up/Down
frequency
16: Pulse train
-
17: High resolution
pulse train (option)
18,19: -
20: Embedded Ethernet
21: RS485
communication
(connector 1)
22: RS485
communication
(connector 2)
23: Communication
option
-
-
0.0 - UL
Hz
0.0 - UL
Hz
0.0 - UL
Hz
-
-
-
-
0: -
1: Reset motor
parameters (0 after
execution)
2: Auto-tuning at run
command (0 after
execution)
3: Auto-tuning at TB ON
4: Motor parameters
auto calculation (0
-
after execution)
5: 4+2 (0 after
execution)
6: Auto-tuning at run
command during TB
ON
7: Auto-tuning F402 only
at run command
during TB ON
0 - 250
%
0.1 - 30.00
%
11-21
Write
Minimum
during
setting unit
Default
run-
(Panel/Commu-
setting
*6
nication)
ning
-
0
N
-
-
-
0.0
Y
0.0
Y
0.2
Y
-
-
-
-
-
-
-
0
N
70
Y
Y
*1
11. Table of parameters
E6582062
User
Reference
setting
1
[5. 2. 8]
3
[6. 21]
-
[6. 9]
9
-
10
-
11
[6. 23. 1]
[6. 23. 2]
[6. 23. 1]
[6. 23. 1]
[6. 23. 2]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents