Setting Acceleration/Deceleration Time - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

5. 1. 4
<ACC: Acceleration time 1>
Basic parameter
<dEC: Deceleration time 1>
Basic parameter
4
5
■ Function
Set a time for acceleration and deceleration.
In <ACC: Acceleration time 1>, set a time before the output frequency of the inverter reaches the
value of <FH: Maximum frequency> from 0.0 Hz.
In <dEC: Deceleration time 1>, set a time before the output frequency of the inverter decreases to
9
0.0 Hz from the value of <FH: Maximum frequency>.
Unit for a setting time is selected with <F519: Unit of Acc/Dec time>.
■ Parameter setting
Title
ACC
dEC
*1
The default is 10.0/30.0/60.0 (s) depending on the capacity. Refer to [11. 6].
Title
F519
5. [Fundamental operation] How to use parameters

Setting acceleration/deceleration time

Easy mode
Easy mode
Parameter name
Acceleration time 1
Deceleration time 1
Parameter name
Unit of Acc/Dec time
ACC
Min: 0.0
X1000
dEC
Min: 0.0
X1000
Adjustment range
0.0 - 6000 (600.0)
0.0 - 6000 (600.0)
Adjustment range
0: -
1: 0.01s unit (0 after execution)
2: 0.1s unit (0 after execution)
5-12
E6582062
STOP
0.0Hz
15:09
:Acceleration time 1
10.0
s
Max: 6000.0
X100
X10
X1
STOP
0.0Hz
15:10
:Deceleration time 1
10.0
s
Max: 6000.0
X100
X10
X1
Unit
Default setting
s
*1
s
*1
Default
setting
0