Toshiba TOSVERT VF-AS3 Instruction Manual page 141

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

8
Select <CMOd: Run command select> and press
the [OK] key.
You can also select <CMOd: Run command
select> on the [Easy mode] screen.
The setting screen is displayed.
9
Select "0: Terminal" and press the [OK] key.
The basic parameter screen is displayed.
Check that the setting value of <CMOd: Run
command select> is "0."
10 Select <FMOd: Frequency command select 1> and press the [OK] key.
The setting screen is displayed.
11 Select "1: Terminal RR" and press the [OK] key.
: Run command select
CMOd
: Frequency command select 1
FMOd
: V/f Pattern
Pt
: Manual torque boost 1
vb
: Base frequency 1
vL
CMOd :Run command select
1: Operation panel,Ext panel
2: Embedded Ethernet
3: RS485 com (connector 1)
4: RS485 com (connector 2)
5: Communication option
CMOd :Run command select
0: Terminal
1: Operation panel,Ext panel
2: Embedded Ethernet
3: RS485 com (connector 1)
4: RS485 com (connector 2)
FMOd :Frequency command select 1
0: -
1: Terminal RR
2: Terminal RX
3: Terminal Ⅱ
4: Terminal AI4(option)
4-33
4. [Basic operation] Operation methods of motor
E6582062
STOP
0.0Hz
15:51
Basic parameters
1
10
0
4.80%
60.0Hz
STOP
0.0Hz
15:51
STOP
0.0Hz
15:51
STOP
0.0Hz
15:55
3
4
9