13. 2 How to reset trip

• Reset the inverter that has tripped after eliminating the cause of the trip.
If it is not eliminated, the inverter will trip again even after reset. Pay enough attention.
Important
The inverter can be reset with the following four methods after a trip occurs.
(1)

Panel operation

You can reset from the operation panel even if terminal run or communication run is per-
formed when the trip occurs.
The following is the reset procedure.
1
Press the [STOP/RESET] key with the trip dis-
played.
"CLr" blinks in the main area, and "Trip reset?
(STOP-Key)" is displayed on the lower side.
• The backlight is red.
(It is white when the setting of the backlight is
changed.)
2
When you press the [STOP/RESET] key again while "CLr" is blinking, the trip is reset.
The display on the screen once disappears, and the screen immediately after power on is dis-
played.
The backlight returns to while.
(2)

Terminal input (external signal)

Short the terminal [RES] and then open.
The inverter is reset when the terminal is opened.
In the default setting, the function "8: Reset 1" is assigned to the terminal [RES].
To reset with other input terminal, assignment of the reset function is required.
(3)
Communication
For details, refer to "RS485 Communication Function Instruction Manual".
(4)

Turning off power

Turn OFF the power and then turn it ON again.
When the power is off, some contents of the monitor at the time of the trip are lost.
Easy
13-13
E6582062
TRIP
0.0Hz
13:13
Top View Mode
CLr
Trip reset ? (STOP-Key)
Copy
Monitor
13. Trip information and measures
I
II
III
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents