6. 37 Select EASY key function

<F750: EASY key function>
LED extension panel option
■ Function
This parameter is valid when the [EASY] key exists (extension panel, etc.)
Since the operation panel of this inverter has no [EASY] key, values other than "0", "2" are invalid
4
even if they are set with <F750>.
When the [EASY] key exists, the following four functions can be selected.
4
• [Easy mode]/[Setting mode] switching
• Shortcut key function
6

• Hand/Auto switching

• Monitor peak and minimum hold trigger
For options such as the extension panel, refer to [10. 3].
■ Parameter setting
Title
9
F750
■ Difference between the settings
0: Easy/Setting mode switching
When you press the [EASY] key while the inverter is stopped, the [Setting mode] and [Easy mode]
can be switched.
In the default setting, the [Setting mode] is set at the time of power on.
The display of parameter setting varies depending on the mode. For details, refer to [4. 2. 1].

1: Shortcut function (Extension panel only)

Parameters whose settings are frequently changed can be registered as shortcuts so that they can
be read out easily with one operation.
Shortcuts are valid only in [Standard mode]
After setting <F750: EASY key function> to "1", read the setting value of the parameter to be stored
and press the [EASY] key for two seconds or more. Now shortcut registration is complete.
To read out the parameter, press the [EASY] key.
2: Hand/Auto switching
You can switch manual (operation panel) and automatic (remote) easily.
After setting <F750: EASY key function> to "2", switch the mode with the [EASY] key.
6. [Advanced] How to use parameters
Parameter name
EASY key function
F750 : EASY key function
0: Easy/Setting mode switching
1: Shortcut function (Ext panel only)
2: Hand/Auto switching
3: Monitor peak & min hold trigger
Adjustment range
0: Easy/Setting mode switching
1: Shortcut function (Extension panel only)
2: Hand/Auto switching
3: Monitor peak and minimum hold trigger
6-180
E6582062
STOP
0.0Hz
14:17
Default setting
0