Motor Parameters Setting; Setting Induction Motor Parameters - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 23 Setting of motor parameters
Prohibited
4
Mandatory
action
4
6. 23. 1
6
<F400: Offline auto-tuning>
<F401: Slip frequency gain>
<F402: Automatic torque boost>
<F403: Online auto-tuning>
<F405: Motor rated capacity>
<F412: Leakage inductance>
9
<F413: Exciting current coefficient>
<F414: Stall prevention coefficient>
<F415: Motor rated current>
<F416: Motor no load current>
<F417: Motor rated speed>
<F459: Load inertia ratio>
<F462: Speed reference filter coefficient 1>
<F465: Speed reference filter coefficient 2>
■ Function
To select vector control, automatic torque boost, or automatic energy-saving with <Pt: V/f Pattern>,
you must set motor parameters (auto-tuning).
There are four setting methods.
• Use <AU2: Torque boost macro> to set both <Pt> and <F400: Offline auto-tuning>.
• Set <Pt> and <F400> individually.
• Set <Pt> and <F400> individually. Perform an auto-tuning after calculating the motor parameter
automatically (available with motor not connected).
6. [Advanced] How to use parameters
• Do not touch terminals or motor of the inverter while performing auto tuning.
Touching the terminals or motor while voltage is applied to the terminals and motor may result
in electric shock, even if the motor is stopped.
After setting offline auto-tuning (F400 = "2"), execute the auto tuning at first start of the inverter.
The auto tuning takes several seconds and the motor is stopped meanwhile, but voltage is
applied to the terminals and motor. The motor may also generate a sound during the auto tun-
ing, but this is not malfunction.
• Install circuit protection such as the mechanical brake in the crane.
If there is no sufficient circuit protection installed in the crane, insufficient motor torque while
auto tuning will cause the machine stalling/falling.

Setting induction motor parameters

WARNING
F400 : Offline auto-tuning
0: -
1: Reset motor parameters
2: Auto-tuning at run command
3: Auto-tuning at TB ON
4: Motor parameters auto calc
F401 : Slip frequency gain
Min: 0
X1000
6-82
E6582062
STOP
0.0Hz
13:37
STOP
0.0Hz
13:38
70
%
Max: 250
X100
X10
X1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents