Standard Connection Diagram - Toshiba TOSVERT VF-S11 Instruction Manual

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

2.2.1
This diagram shows a standard wiring of the main circuit.
2
Main circuit power supply
200V class: three-phase 200-240V
-50/60Hz
400V class: three-phase 380-500V
-50/60Hz
MCCB(2P)
Power supply
R/L1
1 200 240V
-50/60Hz
S/L2
*1: The T/L3 terminal is not provided
for single-phase models.
Use the R/L1 and S/L2 terminal
as input terminals.
*2: The inverter came with the PO
and the PA/+ terminals shorted by
means of a shorting bar.
Before installing the DC reactor (DCL),
remove the bar.
*3: When using the OUT output terminal in
sink logic mode, short-circuit the NO and
CC terminals.

Standard connection diagram 1

Standard connection diagram - sink (common:CC)
DC reactor (DCL)
*2 (option)
MCCB
R/L1
S/L2
Noise
T/L3
filter
*1
FLC
FLB
Protective function
activation output
FLA
RY
Low-speed
signal output
RC
FM
+
Meter
Frequency
meter
(ammeter)
-
P0
PA/+
PB
PC/-
Main circuit
Control
circuit
RES
VF-S11
S1
Operation panel
S2
Connector for
common serial
S3
communications
SW1
FM
VIA
CC
SOURCE
V
V
P24
PLC
OUT
NO
SINK
I
I
CC
CC VIA
VIB PP
External potentiometer (1~10k )
(or input voltage signal across VIB-CC terminals: 0-10V)
B-4
Braking resistor (option)
Motor
U/T1
V/T2
I M
W/T3
F
Forward (rotation signal)
R
Reverse (rotation signal)
Reset
Preset-speed 1
Preset-speed 2
Preset-speed 3
Common
Speed reach
signal output
Ry
*3
+
Voltage signal: 0-10V
-
(Current signal: 4-20mA)
E6581158

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents