13. Trip information and measures
Failure
Trip name
code
002D
Abnormal
1) When <Pt: V/f Pattern> = "0" to "9", an
speed error
over speed condition occurred.
2) When <Pt: V/f Pattern> = "10" to "11",
over speed continued by PG failure,
etc.
3) Due to overvoltage limit operation, the
output frequency exceeded
<FH: Maximum frequency>
+12 Hz or <FH> + <vL: Base frequency
1> x 0.1.
0032
Analog input
The input level of the terminal [II] became
disconnect-
the setting value or less of <F633: II
ing *
analog input disconnection detection
level>
0033
CPU commu-
Communication error between control
nication error
CPU.
0034
Over torque
• The setting value of the <F402: Auto-
boost
matic torque boost> is very high.
• Impedance on the motor is low.
0035
CPU1 fault B
Control CPU fault.
0036
Embedded
Fault in the embedded Ethernet.
Ethernet fault
0037
Option fault
Fault in the option connected to slot A.
(slot A)
0038
Option fault
Fault in the option connected to slot B.
(slot B)
0039
Option fault
Fault in option 3.
(slot C)
003A
CPU2 fault
Control CPU fault.
003D
Control power
1) Failure on the control power supply
option failure *
option.
2) The setting of <F647: Control power
option failure detection> is improper.
003F
Rush current
1) Fault on the rush current suppression
suppression
relay.
relay fault
2) The power was turned ON/OFF
frequently.
*Enable/Disable can be selected for trip with a parameter.
0040
PTC failure
1) PTC protection for the motor became
enabled.
2) Failure in the PTC circuit.
Detection factor
1) 3)
• Check whether a problem exists in input
• When the regenerative energy is large,
2) Check the PG wiring and setting.
• Check that the signal line connected to
• Check if the <F633> setting is correct.
Turn off the power and then turn it on
again.
If the error occurs again, contact your
Toshiba distributor.
Set the motor parameters according to the
motor characteristic, and perform auto-
tuning.
<vL: Base frequency 1>,
<vLv: Base frequency voltage>,
<F405: Motor rated capacity>,
<F415: Motor rated current>,
<F417: Motor rated speed>,
<F400: Offline auto-tuning>, etc.
Fault in internal inverter.
Contact your Toshiba distributor.
Fault in internal inverter.
Contact your Toshiba distributor.
Fault in the option.
Contact your Toshiba distributor.
Fault in the option.
Contact your Toshiba distributor.
Fault in the option.
Contact your Toshiba distributor.
Fault in internal inverter.
Contact your Toshiba distributor.
1) When input voltage of the control power
Contact your Toshiba distributor.
2) When the control power supply option is
not used, set <F647> = "0".
1) Fault in internal inverter.
2) Instead of turning ON/OFF with the
1) Check the motor and PTC.
2) Failure in internal inverter.
13-2
E6582062
Measures
voltage.
install a braking resistor (option).
the terminal [II] is not disconnected.
supply is normal and the voltage
between terminals [+SU]-[CC] is under
20 Vdc, it is a failure in the control
power supply option.
Contact your Toshiba distributor.
power supply, turn ON/OFF with a run
command.
Contact your Toshiba distributor.