■ Function
4
You can return parameters to their default settings at a time, clear run times, and store/rewrite
parameters specified by users.
5
■ Parameter setting
Title
tyP
9
Note) The setting value becomes 0 after execution, but a check mark is added to the previous
setting value.
5. [Fundamental operation] How to use parameters
Returning parameters to their default settings
Clearing each history
Parameter name
Default setting
Typ : Default setting
0: -
1: 50Hz setting
2: 60Hz setting
3: Default setting 1
4: Clear past trips
Adjustment range
0: -
1: 50Hz setting
2: 60Hz setting
3: Default setting 1
4: Clear past trips
5: Clear cumulative run time
6: Initialize typeform
7: Store user settings
8: Rewrite user settings
9: Clear cumulative fan run time
10, 11: -
12: Clear number of starting
13: Default setting 2 (complete initialization)
14: Clear number of external equipment
starting
5-28
E6582062
STOP
0.0Hz
15:19
Default
setting
0