Standard Connection Diagram - Toshiba TOSVERT VF-MB1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

2.2.1
This diagram shows a standard wiring of the main circuit.
2
Main circuit power supply
1ph-240V class: single-phase 200-240V
3ph-500V class: three-phase 380-500V
Single
phase
Power
supply
*1: Set the slide switch SW1 to sink side.
Refer to page B-11,12 for details.
Default setting is PLC side.
*2: The T/L3 terminal is not provided for
single-phase models.
Use the R/L1 and S/L2/N terminals as
input terminals.
*3: When using the OUT output terminal in
sink logic mode, short the NO and CC
terminals.
*4: When VIA or VIB terminal is used as logic
input terminal, refer to section 7.2.1.
*5: To supply control power from an external
power supply for backing up the control
power supplied from the inverter, an optional
control power backup device (CPS002Z) is
required. In such a case, the backup device
is used at the same time with the internal
power supply of the inverter.
The optional control power backup unit can
be used with both 240V and 500V models.
*6: When STO terminal is used as compliance with
safety standards, refer to section 9.3.

Standard connection diagram 1

Standard connection diagram - SINK (Negative) (common:CC)
*2
MCCB
R/L1
S/L2
-50/60Hz
T/L3
-50/60Hz
*6
Control power
supply
MCCB(2P)
*5
R/L1
S/L2/N
Protective function
activation output
Low-speed
signal output
Meter
7.5V-1mA
(or 0-10V/0(4)-20mA)
PA/+ PC/-
PBe
Noise
Power circuit
filter
STO
+SU
Control
VF-MB1
circuit
FLA
FLB
FLC
Operation panel
SW1
*1
SOURCE
RY
PLC
SINK
RC
RS485
SW2(S3)
connector
LOGIC
PTC
*4
*4
FM
CC
VIC
VIB
VIA
+
Frequency
meter
(ammeter)
-
External potentiometer (1k-10k)
(or voltage signal between VIA and CC: 0-10V)
B-4
E6581697
Braking resistor(Option)
PB
Motor
U/T1
V/T2
M
W/T3
F
Forward run command
R
Reverse run command
RES
Reset
S1
Preset-speed command 1
S2
Preset-speed command 2
S3
Preset-speed command 3
CC
Common
P24
Speed reach
signal output
OUT
Ry
NO
*3
CC
PP
Current signal: 4(0)-20mA
Voltage signal: 0-+10V
(or -10-+10V)