The amount of forcible air-cooling ventilation required and the necessary heat discharge surface
quantity when operating in a sealed cabinet depending on motor capacity are as follows.
<ND rating>
Applicable
Input
motor
voltage
Inverter type-form
capacity
Class
(kW)
0.75
1.5
2.2
4.0
5.5
7.5
11
3-phase
15
VFAS3-
240 V
18.5
22
30
37
45
55
75
*1
Case of 100% load ND continuous operation. The heat loss for the optional external devices (input reactor, radio noise reduction filters, etc.) is not
included in the calorific values in the table.
Inverter
Frame
calorific value
size
(W) *1
2004P
65
2007P
92
A1
2015P
115
2022P
189
2037P
A2
243
2055P
392
A3
2075P
544
2110P
625
2150P
A4
750
2185P
874
2220P
1084
2300P
A5
1384
2370P
1631
2450P
2466
A6
2550P
3432
2-7
Forced
air-cooled
Inner side
Required
calorific value
ventilation
(W) *1
amount
3
(m
/min)
27
0.37
29
0.52
32
0.65
38
1.07
47
1.38
53
2.22
62
3.09
90
3.55
101
4.26
112
4.96
136
6.15
163
7.86
184
9.26
278
14.00
359
19.48
2. Installation and wiring
E6582062
Sealeded
cabinet
Necessary
heat discharge
surface
2
quantity (m
)
1.30
2
1.83
2.31
3
3.79
4.85
7.84
10.87
12.51
15.01
17.49
21.68
27.68
32.63
49.33
68.64
9