Standard Connection Diagram - Toshiba TOSVERT VF-nC3 Instruction Manual

Hide thumbs Also See for TOSVERT VF-nC3:
Table of Contents

Advertisement

2.2.1
This diagram shows a standard wiring of the main circuit.
2
Main circuit power supply
3ph-240V class: three-phase 200-240V
1ph-240V class: single-phase 200-240V
1ph-120V class: single-phase 100-120V
MCCB(2P)
Single phase
Power supply
*1: The T/L3 terminal is not provided for
single-phase models.
Use the R/L1 and S/L2 terminal as
input terminals.
*2: The inverter is supplied with the PO and
the PA/+ terminals shorted by means of
a shorting-bar.
Before installing the DC reactor (DCL),
remove the bar.
*3: When using the OUT output terminal in sink
logic mode, short the NO and CC terminals.
*4: 1ph-240V models have noise filter inside.
*5: 1ph-120V models cannot be used with
DC reactors.
*6: When external potentiometer is connected
by using P5 terminal, set the parameter
f109=3.
*7: When VI terminal is used as a logic
input terminal, refer to page B-12.

Standard connection diagram 1

Standard connection diagram - SINK (Negative) (common:CC)
DC reactor (DCL)
*2 , *5 (option)
MCCB
R/L1
S/L2
-50/60Hz
T/L3
-50/60Hz
*1
-50/60Hz
Protective function
R/L1
activation output
S/L2/N
Meter
(or 0-10V/4-20mA)
P0
PA/+
Noise
Power circuit
filter
*4
Control
circuit
FLA
VF-nC3
FLB
FLC
Operation panel
RS485
communication
connector
*7
FM
CC
VI
+
Frequency
meter
(ammeter)
-
External potentiometer (1k-10k)
7.5V-1mA
B-4
E6581595
PC/-
Motor
U/T1
V/T2
I M
W/T3
F
Forward run command
R
Reverse run command
S1
Preset-speed command 1
S2
Preset-speed command 2
Common
CC
P24
OUT
Ry
NO
*3
CC
P5
+
Voltage signal: 0-5V/0-10V
-
(Current signal: 4-20mA)
*6
Low-speed
signal output