6. 30. 7
<F610: Undercurrent trip>
<F609: Undercurrent detection hysteresis>
<F611: Undercurrent detection level>
<F612: Undercurrent detection time>
■ Function
Trips or outputs an alarm when the output current falls to the value set in <F611: Undercurrent
4
detection level> or less for the time specified in <F612: Undercurrent detection time>.
Hysteresis can be set by <F609: Undercurrent detection hysteresis> The trip display is "UC".
4
■ Parameter setting
6
Title
F610
F609
F611
9
F612
■ Difference depending on the setting of <F610: Undercurrent trip>
0: Disabled
A trip does not occur. (Failure signal FL disabled)
Undercurrent (UC) alarm can be output from the output terminal.
Assign "26: Undercurrent (UC) alarm" to an unused output terminal.
1: Enabled
When a current level set in <F611: Undercurrent detection level> or less is detected for the period of
time set in <F612: Undercurrent detection time> or more, the inverter trips and "UC" is displayed.
(Failure signal FL enabled)
■ Setting example
Set "26: Undercurrent (UC) alarm" to the unused output terminal.
In the case of <F610: Undercurrent trip> = "0: Disabled", the signal can be output from the output
terminal as follows.
6. [Advanced] How to use parameters

Undercurrent detection

Parameter name
Undercurrent trip
Undercurrent detection
hysteresis
Undercurrent detection
level
Undercurrent detection
time
F610 : Undercurrent trip
0: Disabled
1: Enabled
Adjustment range
0: Disabled
1: Enabled
1 - 20
0 - 150
0 - 255
6-128
E6582062
STOP
0.0Hz
13:55
Unit
Default setting
0
%
10
%
0
s
0