Standard Connection Diagram - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

2.2.1
This diagram shows a standard wiring of the main circuit.
2
Main circuit power supply
3ph-200-240V class: three-phase 200-240V
1ph-200-240V class: single-phase 200-240V
3ph-380-500V class: three-phase 200-240V
Single
MCCB(2P)
phase
power
supply
*1: The T/L3 terminal is not provided for
single-phase models.
Use the R/L1 and S/L2/N terminals as
input terminals.
*2: The inverter is supplied with the PO and
the PA/+ terminals shorted by means of
a shorting bar.
Before installing the DC reactor (DCL),
remove the bar.
*3: When using the OUT output terminal in
sink logic mode, short the NO and CC
terminals.
*4: When VIA or VIB terminal is used as
logic input terminal, refer to section
7.2.1.
*5: To supply control power from an
external power supply for backing up the
control power supplied from the inverter,
an optional control power backup device
(CPS002Z) is required. In such a case,
the backup device is used at the same
time with the internal power supply of
the inverter.
The optional control power backup unit
can be used with both 240V and 500V
models.
*6: Set the slide switch SW1 to SINK side.
Default setting is PLC side.
*7: When STO terminal is used as
compliance with safety standards, refer
to Safety function manual (E6581860).

Standard connection diagram 1

Standard connection diagram – SINK (Negative) (common: CC)
DC reactor (DCL)
*2 (option)
*1
MCCB
R/L1
-50/60Hz
S/L2
-50/60Hz
T/L3
-50/60Hz
STO
*7
Control power
+SU
supply
*5
R/L1
VF-S15
S/L2/N
FLA
FLB
Protective function
activation output
FLC
RY
Low-speed
signal output
RC
FM
Meter
Frequency
meter
(ammeter)
1mA
(or 0(4)-20mA/0-10V)
P0
PA/+
PB
PC/-
Noise
Power circuit
filter
Control
circuit
RES
S1
S2
S3
Operation panel
CC
P24
SW1 *6
SINK
SOURCE
OUT
PLC
NO
RS485
connector
SW2
CC
S4
VIB
S3
PTC
*4
*4
CC
VIC
VIB
VIA
PP
External potentiometer (1k-10kΩ)
(or voltage signal between VIA and CC: 0-10V)
B-4
E6582175
Braking resistor (Option)
Motor
U/T1
V/T2
M
W/T3
F
Forward run command
R
Reverse run command
Reset
Preset-speed command 1
Preset-speed command 2
Preset-speed command 3
Common
Speed reach
Signal output
Ry
*3
Current signal: 4(0)-20mA
Voltage signal: 0-+10V
(or -10-+10V)