Timing Chart (Setting Example) - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

■ Timing chart (setting example)

MC applying for inverter
Commercial power/Inverter Switching 1 (Terminal [R1])
MC applying for commercial power run
Commercial power/Inverter Switching 2 (Terminal [R2])
Commercial power run switching (Terminal [S3])
When function numbers "102", "103" (switch to commercial power run) is set to terminal [S3].
4
Terminal [S3] ON: commercial power operation
Terminal [S3] OFF: inverter operation
4
Switching cannot be performed properly if standby function is OFF.
6
Title
F354
F355
F356
9
F357
F358
F116
F133
F134
*1
Depending on capacity. For details, refer to [11. 6].
Important
6. [Advanced] How to use parameters
<F355: Commercial power
switching frequency>
Setting frequency
<F357: Commercial power
switching wait time>
Input terminal (Standby)
Parameter name
Commercial power/
Inverter switching
Commercial power
switching frequency
Inverter switching wait
time
Commercial power
switching wait time
Commercial power
switching frequency
continuous time
Terminal S3 function
Terminal R1 function 1
Terminal R2 function
• To allow switching to commercial power operation, forward run of the inverter and the direction
of rotation of the motor for commercial power operation must match.
• Do not set <F311: Reverse inhibited> to "2: Fwd inhibited". The inverter will not be able to for-
ward run and switching to commercial power cannot be accomplished.
• This function can only be used in induction motors. Do not use this function with PM motors.
<F358: Commercial power switching
frequency continuous time>
<F356: Inverter switching
wait time>
ON
ON
ON
ON
Setting example
2: Switch at F355 or 3: Switch at trip and at
F355
Power supply frequency, etc.
*1
Depending on capacity
0.62
2.00
102: Commercial powr run switching
46: Commercial power/Inverter Switching 1
48: Commercial power/Inverter Switching 2
6-78
E6582062
Time needed for
speed detection
ON
-
Hz
s
s
s
-
-
-
Unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents