Toshiba TOSVERT VF-AS3 Instruction Manual page 413

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Title
Parameter name
F814
Communication point 2
frequency
F820
RS485 (2) baud rate
F821
RS485 (2) parity
F823
RS485 (2) time-out time
*2
F824
RS485 (2) time-out
operation
F825
RS485 (2) transmission
wait time
F826
RS485 (2) inverter to
inverter communication
F827
RS485 (2) protocol
F828
RS485 (2) time-out
detection
F829
RS485 (2) wiring type
F830
MODBUS continuous
address
F856
Motor pole number for
communication
Adjustment range
0.0-FH
*1
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: -
*1
0: Disabled
1: Even parity
2: Odd parity
0.0: Disabled
0.1 - 100.0
0: Continue running
*2
2, 3: -
4: Trip
5: -
6: Trip after Deceleration stop
0.00 - 2.00
0: Follower (0Hz command when Leader
fails)
*1
1: Follower (continue running when Leader
fails)
2: Follower (emergency off when Leader
fails)
3: Leader (transmit frequency command)
4: Leader (transmit output frequency signal)
5: Leader (transmit torque command)
6: Leader (transmit output torque command)
0: TOSHIBA
1: MODBUS
2:
0: Always
1: Run command and frequency command
by communication are enabled.
2: During run by communication
0: 2-wire
1: 4-wire
0: Disabled
1: Enabled
1: 2 pole
2: 4 pole
3: 6 pole
4: 8 pole
5: 10 pole
6: 12 pole
7: 14 pole
8: 16 pole
6-185
E6582062
Unit
Default setting
Hz
*4
50.0/60.0
1
1
0.0
s
0
s
0.00
0
0
1
0
0
2
6. [Advanced] How to use parameters
3
4
6
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents