Switching With Input Terminal F200 = "0"; Automatic Switching With Switching Frequency F200 = "1" - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

■ Switching with input terminal <F200> = "0"
Set <F200: Frequency command priority select> to "0".
Assign "104: FMOd/F207 priority switching" to an unused input terminal. For details, refer to [7. 2. 1].
• When the input terminal is OFF, run the motor with the frequency command set with <FMOd:
Frequency command select 1>.
• When the input terminal is ON, run the motor with the frequency command set with <F207:
Frequency command select 2>.
Frequency set for <FMOd>
Frequency set for <F207>
■ Automatic switching with switching frequency <F200> = "1"
Set <F200: Frequency command priority select> to "1" and set the frequency with <F208:
Frequency command switching frequency>.
• If the frequency command set with <FMOd: Frequency command select 1> is larger than the value
set with <F208>, the value set with <FMOd> becomes the frequency command.
• If the frequency command set with <FMOd> is larger than the value set with <F208>, the value set
with <F207: Frequency command value 2> becomes the frequency command.
Frequency command signal
<F208>
Command set for <FMOd>
given priority
OFF
ON
<FMOd>
<F207>
<FMOd>
<F208>
<FMOd>
Command set for <F207>
given priority
5-67
Frequency command
Time
<F208>
5. [Fundamental operation] How to use parameters
E6582062
3
4
5
9