Setting Method 4: Manually Setting Motor Parameter - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Check the motor name plate and set the following parameters first.
- <vL: Base frequency 1> (Rated frequency)
- <vLv: Base frequency voltage 1> (Rated voltage)
- <F405: Motor rated capacity>
- <F415: Motor rated current>
- <F417: Motor rated speed>
Next, set <Pt: V/f Pattern>. For details of setting methods, refer to [5. 2. 4].
Then, select <F400> = "4: Motor parameters auto calculation (0 after execution)" and calculate
motor parameters automatically.
Motor parameters <F402: Automatic torque boost>, <F412: Leakage inductance>, and <F416:
Motor no load current> will be set automatically.
This setting can be made without connecting the motor since it only calculates.
After automatic setting of motor parameter with <F400> = "4", be sure to set <F400> to "2: Auto-
tuning at run command (0 after execution)" and perform an auto-tuning.
You can set <F400> to "4" and "2" collectively by setting <F400> to "5: 4+2 (0 after excecution)".
Since calculation is performed based on general trend, the calculation results may not be correct. In
this case, set the parameter manually.

■ Setting method 4: Manually setting motor parameter

Set <Pt: V/f Pattern> and set the motor parameter manually.
If tuning error "Etn1" is displayed during auto-tuning setting or when you want to improve vector
control characteristics, set motor parameters individually.
4) Parameter setting
Title
Parameter name
F401
Slip frequency gain
F402
Automatic torque boost
F405
Motor rated capacity
F412
Leakage inductance
F413
Exciting current
coefficient
F415
Motor rated current
F416
Motor no load current
F417
Motor rated speed
F459
Load inertia ratio
F460
Speed control response
1
F461
Speed control
stabilization coefficient 1
F462
Speed reference filter
coefficient 1
F463
Speed control response
1
Adjustment range
0 - 250
0.1 - 30.00
0.10 - 315.0
0.0 - 25.0
100 - 150
*1
10 - 90
100 - 64000
0.1 - 100.0
0.0 - 25.0
0.50 - 2.50
0 - 100
0.0 - 25.0
6-85
E6582062
Unit
Default setting
%
70
%
*1
kW
*1
%
*1
%
100
A
*1
%
*1
-1
*2
min
Times
1.0
-
0.0
-
1.00
-
35
-
0.0
6. [Advanced] How to use parameters
3
4
6
9