6. 2. 3
<F108: Terminal RR input select>
■ Function
This parameter selects the input signal of the terminal
[RR].
4
■ Parameter setting
Title
4
F108
6
9
Reference
6. [Advanced] How to use parameters

Selecting input signal of the terminal [RR]

Parameter name
Terminal RR input select
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
F108 : Terminal RR input select
1: Voltage input (0-10V)
2: -
3: -
4: PTC input
5: PT100(2-wire)input
Adjustment range
1: Voltage input (0-10 V)
2, 3: -
4: PTC input
5: PT100 (2-wire) input
6: -
7: PT1000 (2-wire) input
8: -
9: KTY84 input
6-10
E6582062
STOP
0.0Hz
12:46
Default setting
1