2) In case of torque limit

If, during power running, the output torque reaches the value for <F441: Power running torque
limit level 1> or more, and continues for the period of time set for <F452: Stall detection time
during power running>, the trip "Ot2" will occur.
• How to operate the operation panel -> Refer to [3. 1. 1].
Reference
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
Output frequency (Hz)
Output torque (%)
<F441>
Below
<F452>
<F452>
6-105
"0t2" Trip
Time (s)
Time (s)
6. [Advanced] How to use parameters
E6582062
3
4
6
9