Output Terminal Parameter Setting - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Frequency command value
<F100: Low-speed signal

■ Output terminal parameter setting

Low-speed signal is the default setting for terminal [R1].
4
Title
F133
4
*1
For details on the output terminal functions, refer to [7. 2. 2].
6
Memo
9
Reference
6. [Advanced] How to use parameters
Output frequency (Hz)
output frequency>
0
[R1A]-[R1C] output
(Low-speed signal)
Parameter name
Terminal R1 function 1
• When you want to output the inversion signal (OFF signal), set "5".
• The signals can be also output from the other output terminals depending on the parameter
setting.
When you want to output the signals from the relay logic output terminals [FLA]-[FLB]-[FLC],
set "4" or "5" for <F132: Terminal FL function>. When you want to output the signals from the
terminals [R2A]-[R2C], set "4" or "5" for <F134: Terminal R2 function>. When you want to
output the signals from the terminal [FP], set "4" or "5" for <F130: Terminal FP function 1>.
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
• Details on operation by external signals -> Refer to [Chapter 7].
Adjustment range
*1
0-255
6-2
E6582062
Time (s)
ON
OFF
Default setting
4