Forced Run Control In Emergency; Setting The Parameters And Input Terminal; Signal Output Of Forced Run - Toshiba TOSVERT VF-AS3 Instruction Manual

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

6. 31 Forced run control in emergency

<F650: Forced run>
■ Function
With the forced run control, the motor runs at the specified speed in an emergency.
■ Parameter setting
Title
Parameter name
F650
Forced run
F294
Preset speed 15 / Forced
run speed

■ Setting the parameters and input terminal

Set <F650: forced run> = "1: Enabled"
Set any of the function to the unused input terminal. For details, refer to [7. 2. 1].
You can perform the forced run or fire speed run with the setting of <F650> = "1" and an assigned
input terminal is ON.
 "56: Forced run"
• Once the input signal is ON, it is self-retained. The motor runs at the frequency set by
<F294>.
• In case of a slight failure, the motor performs the forced run, in which the operation is continued.
 "58: Fire speed run"
• Once the input signal is ON, it is self-retained. The motor performs the fire speed run at the
frequency set by <F294>.
In both cases, to stop the running, the power circuit needs to be turned off.
During the forced run and the fire speed run, "FirE" is displayed.

■ Signal output of forced run

Assign any of these to the unused output terminal. For details, refer to [7. 2. 2].
 "138: During forced run"
 "140: During fire speed run"
F650 : Forced run
0: Disabled
1: Enabled
Adjustment range
0: Disabled
1: Enabled
LL - UL
6-153
E6582062
STOP
0.0Hz
14:07
Unit
Default setting
0
Hz
0.0
6. [Advanced] How to use parameters
3
4
6