And Function Block - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Table 391:
TIMERSET Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
t
0.000 - 90000.000
13.4.1.9
Technical manual
Settings
Unit
Step
-
-
s
0.001

AND function block

Identification
Function description
AND function block
Functionality
The AND function is used to form general combinatory expressions with boolean
variables. The AND function block has four inputs and two outputs.
Default value on all four inputs are logical 1 which makes it possible for the user to just
use the required number of inputs and leave the rest un-connected. The output OUT has
a default value 0 initially, which suppresses one cycle pulse if the function has been put in
the wrong execution order.
Function block
AND
INPUT1
OUT
INPUT2
NOUT
INPUT3
INPUT4
IEC09000289-1-en.vsd
IEC09000289 V1 EN
Figure 269:
AND function block
Signals
Table 392:
AND Input signals
Name
Type
INPUT1
BOOLEAN
INPUT2
BOOLEAN
INPUT3
BOOLEAN
INPUT4
BOOLEAN
Default
Description
Disabled
Operation Disabled/Enabled
0.000
Delay for settable timer n
IEC 61850
IEC 60617
identification
identification
AND
Default
Description
1
Input signal 1
1
Input signal 2
1
Input signal 3
1
Input signal 4
Section 13
Logic
ANSI/IEEE C37.2
device number
-
-
551