1MRK 506 335-UUS A
Technical manual
3I
<0.1 · IBase
0
or
3I
<maxIph · INRelPG
0
where:
|3V
|
is the magnitude of the zero sequence voltage
0
V
|
is the magnitude of the positive sequence voltage
1
V
|
is the magnitude of the negative sequence voltage
2
maxIph
is the maximal phase current
Phase-to-phase fault detection
The detection of phase-to-phase fault is performed by evaluation of the angle difference
between the sequence voltages V
C-A sector
VB
180°
A-B sector
ANSI06000383 V2 EN
Figure 67:
Definition of fault sectors for phase-to-phase fault
The phase-to-phase loop for the faulty phases will be determined if the angle between the
sequence voltages V
and V
2
following conditions are fulfilled:
|V
|>V1MinOP
1
|V
|>V2MinOp
2
where:
V1MinOP and V2MinOp
are the setting parameters for positive sequence and negative sequence
minimum operate voltages
and V
.
2
1
60°
VC
VA (Ref)
B-C sector
VA
300°
ANSI06000383-2-en.vsd
lies within the sector defined according to figure
1
Section 6
Impedance protection
67
and the
153