1MRK 506 335-UUS A
6.3.5
Table 39:
FMPSPDIS Group settings (basic)
Name
Values (Range)
IMaxLoad
10 - 5000
RLd
1.00 - 3000.00
LdAngle
5 - 70
BlinderAng
5 - 90
Table 40:
FMPSPDIS Group settings (advanced)
Name
Values (Range)
DeltaIMinOp
5 - 100
DeltaVMinOp
5 - 100
V1Level
5 - 100
I1LowLevel
5 - 200
V1MinOp
5 - 100
V2MinOp
1 - 100
INRelPG
10 - 100
3I0BLK_PP
10 - 100
Table 41:
FMPSPDIS Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
6.3.6
6.3.6.1
Technical manual

Settings

Unit
Step
%IB
1
ohm/p
0.01
Deg
1
Deg
1
Unit
Step
%IB
1
%VB
1
%VB
1
%IB
1
%VB
1
%VB
1
%IB
1
%IB
1
Unit
Step
-
1
Operation principle
The phase selection function
Faulty phase identification with load encroachment for mho (FMPSPDIS, 21) function
can be decomposed into six different parts:
Default
Description
200
Maximum load for identification of three phase
fault in % of IBase
80.00
Load resistive reach in ohm/phase
20
Load encroachment inclination of load angular
sector
80
Blinder angle
Default
Description
10
Delta current level in % of IBase
20
Delta voltage level in % of Vbase
80
Positive sequence voltage limit for
identification of three phase fault
10
Positive sequence current level for
identification of three phase fault in % of IBase
20
Minimum operate positive sequence voltage
for phase selection
5
Minimum operate negative sequence voltage
for phase selection
20
3I0 limit for release Phase-Ground measuring
loops in % of maximum phase current
40
3I0 limit for blocking Phase-to-Phase
measuring loops in % of maximum phase
current
Default
Description
1
Selection of one of the Global Base Value
groups