Section 12
Scheme communication
12.2.5
Table 339:
ZCRWPSCH (85) Group settings (basic)
Name
Values (Range)
CurrRev
Disabled
Enabled
tPickUpRev
0.000 - 60.000
tDelayRev
0.000 - 60.000
WEI
Disabled
Echo
Echo & Trip
tPickUpWEI
0.000 - 60.000
PU27PP
10 - 90
PU27PN
10 - 90
Table 340:
ZCRWPSCH (85) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
504
Name
Type
BLKZ
BOOLEAN
CBOPEN
BOOLEAN
CRL
BOOLEAN
Table 338:
ZCRWPSCH (85) Output signals
Name
Type
IRVL
BOOLEAN
TRWEI
BOOLEAN
ECHO
BOOLEAN

Settings

Unit
Step
-
-
s
0.001
s
0.001
-
-
s
0.001
%VB
1
%VB
1
Unit
Step
-
1
Default
Description
0
Block of trip from WEI logic through the loss of voltage
(fuse-failure) function
0
Block of trip from WEI logic by an open breaker
0
POTT or Unblock carrier receive for WEI logic
Description
Operation of current reversal logic
Trip of WEI logic
A signal that indicates channel start (CS) by WEI logic
Default
Description
Disabled
Operating mode of Current Reversal Logic
0.020
Pickup time for current reversal logic
0.060
Time Delay to prevent Carrier send and local
trip
Disabled
Operating mode of WEI logic
0.010
Coordination time for the WEI logic
70
Phase to Phase voltage for detection of fault
condition
70
Phase to Neutral voltage for detection of fault
condition
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 335-UUS A
Technical manual