Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 14
Monitoring
14.19.3
14.19.4
Table 516:
I103MEAS Non group settings (basic)
Name
Values (Range)
FunctionType
1 - 255
MaxIL1
1 - 99999
MaxIL2
1 - 99999
MaxIL3
1 - 99999
MaxIN
1 - 99999
MaxUL1
0.05 - 2000.00
MaxUL2
0.05 - 2000.00
MaxUL3
0.05 - 2000.00
MaxUL1-UL2
0.05 - 2000.00
MaxUN
0.05 - 2000.00
MaxP
0.00 - 2000.00
MaxQ
0.00 - 2000.00
MaxF
45.0 - 66.0
696

Signals

Table 515:
I103MEAS Input signals
Name
Type
BLOCK
BOOLEAN
IL1
REAL
IL2
REAL
IL3
REAL
IN
REAL
UL1
REAL
UL2
REAL
UL3
REAL
UL1L2
REAL
UN
REAL
P
REAL
Q
REAL
F
REAL
Settings
Unit
Step
-
1
A
1
A
1
A
1
A
1
kV
0.05
kV
0.05
kV
0.05
kV
0.05
kV
0.05
MW
0.05
MVA
0.05
Hz
1.0
Default
Description
0
Block of service value reporting
0.0
Service value for current phase A
0.0
Service value for current phase B
0.0
Service value for current phase C
0.0
Service value for residual current IN
0.0
Service value for voltage phase A
0.0
Service value for voltage phase B
0.0
Service value for voltage phase C
0.0
Service value for voltage phase-phase AB
0.0
Service value for residual voltage VN
0.0
Service value for active power
0.0
Service value for reactive power
0.0
Service value for system frequency
Default
Description
1
Function type (1-255)
3000
Maximum current phase A
3000
Maximum current phase B
3000
Maximum current phase C
3000
Maximum residual current IN
230.00
Maximum voltage for phase A
230.00
Maximum voltage for phase B
230.00
Maximum voltage for phase C
400.00
Maximum voltage for phase-phase AB
230.00
Maximum residual voltage VN
1200.00
Maximum value for active power
1200.00
Maximum value for reactive power
51.0
Maximum system frequency
1MRK 506 335-UUS A
Technical manual