Pulsetimer Function Block - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 13
Logic
13.4.1.4
Table 381:
PULSETIMER Non group settings (basic)
Name
Values (Range)
t
0.000 - 90000.000
546

PULSETIMER function block

Identification
Function description
PULSETIMER function block
Functionality
The pulse function can be used, for example for pulse extensions or limiting of operation
of outputs. The PULSETIMER has a settable length.
Function block
PULSETIMER
INPUT
OUT
IEC09000291-1-en.vsd
IEC09000291 V1 EN
Figure 263:
PULSETIMER function block
Signals
Table 379:
PULSETIMER Input signals
Name
Type
INPUT
BOOLEAN
Table 380:
PULSETIMER Output signals
Name
Type
OUT
BOOLEAN
Settings
Unit
Step
s
0.001
IEC 61850
IEC 60617
identification
identification
PULSETIMER
Default
Description
0
Input signal
Description
Output signal
Default
Description
0.010
Pulse time length
1MRK 506 335-UUS A
ANSI/IEEE C37.2
device number
-
-
Technical manual