Monitored Data - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
Name
Values (Range)
3I2PU
1 - 100
OpDVDI
Disabled
Enabled
DVPU
1 - 100
DIPU
1 - 100
VPPU
1 - 100
50P
1 - 100
SealIn
Disabled
Enabled
VSealInPU
1 - 100
IDLDPU
1 - 100
VDLDPU
1 - 100
Table 230:
SDDRFUF Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
10.2.6
Technical manual
Unit
Step
%IB
1
-
-
%VB
1
%IB
1
%VB
1
%IB
1
-
-
%VB
1
%IB
1
%VB
1
Unit
Step
-
1

Monitored data

Table 231:
SDDRFUF Monitored data
Name
Type
3I0
REAL
3I2
REAL
3V0
REAL
3V2
REAL
Secondary system supervision
Default
Description
10
Pickup of negative sequence undercurrent
element in % of IBase
Disabled
Operation of change based function Disable/
Enable
60
Pickup of change in phase voltage in % of
VBase
15
Pickup of change in phase current in % of
IBase
70
Pickup of phase voltage in % of VBase
10
Pickup of phase current in % of IBase
Enabled
Seal in functionality Disable/Enable
70
Pickup of seal-in phase voltage in % of VBase
5
Pickup for phase current detection in % of
IBase for dead line detection
60
Pickup for phase voltage detection in % of
VBase for dead line detection
Default
Description
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
-
A
-
A
-
kV
-
kV
Section 10
Description
Magnitude of zero sequence
current
Magnitude of negative
sequence current
Magnitude of zero sequence
voltage
Magnitude of negative
sequence voltage
335

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents