Section 6
Impedance protection
6.2.4
128

Signals

Table 31:
FDPSPDIS Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
DIRCND
INTEGER
Table 32:
FDPSPDIS Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
FWD_A
BOOLEAN
FWD_B
BOOLEAN
FWD_C
BOOLEAN
FWD_G
BOOLEAN
REV_A
BOOLEAN
REV_B
BOOLEAN
REV_C
BOOLEAN
REV_G
BOOLEAN
NDIR_A
BOOLEAN
NDIR_B
BOOLEAN
NDIR_C
BOOLEAN
NDIR_G
BOOLEAN
FWD_1PH
BOOLEAN
FWD_2PH
BOOLEAN
FWD_3PH
BOOLEAN
PHG_FLT
BOOLEAN
PHPH_FLT
BOOLEAN
STCNDZI
INTEGER
DLECND
INTEGER
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
External directional condition
Description
Trip by pilot communication scheme logic
Start in any phase or loop
Fault detected in phaseA - forward direction
Fault detected in phase B - forward direction
Fault detected in phase C - forward direction
Ground fault detected in forward direction
Fault detected in phase A- reverse direction
Fault detected in phase B - reverse direction
Fault detected in phase C - reverse direction
Ground fault detected in reverse direction
Non directional fault detected in Phase A
Non directional fault detected in Phase B
Non directional fault detected in Phase C
Non directional start, Phase-Ground
Single phase-to-ground fault in forward direction
Phase-to-phase fault in forward direction
Pick up in forward direction for three-phase fault
Current conditions release of Phase-Ground measuring
elements
Current conditions release of Phase-Phase measuring
elements
Pick up condition (Z< with LE and/or I> and 3I0 E/F
detection)
Pickup for load encroachment and 3I0
1MRK 506 335-UUS A