Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 14
Monitoring
14.3.6
Table 458:
L4UFCNT Group settings (basic)
Name
Values (Range)
Operation
Disabled
On
CountType
Set
Reset
DBLL or DLLB
CounterLimit1
1 - 65535
CounterLimit2
1 - 65535
CounterLimit3
1 - 65535
CounterLimit4
1 - 65535
MaxValue
1 - 65535
OnMaxValue
Stop
Rollover Steady
Rollover Pulsed
InitialValue
0 - 65535
14.3.7
612
Table 457:
L4UFCNT Output signals
Name
Type
ERROR
BOOLEAN
OVERFLOW
BOOLEAN
LIMIT1
BOOLEAN
LIMIT2
BOOLEAN
LIMIT3
BOOLEAN
LIMIT4
BOOLEAN
VALUE
INTEGER

Settings

Unit
Step
-
-
-
-
-
1
-
1
-
1
-
1
-
1
-
-
-
1
Monitored data
Table 459:
L4UFCNT Monitored data
Name
Type
VALUE
INTEGER
Description
Error indication on counter limit and/or initial value
settings
Overflow indication on count of greater than MaxValue
Counted value is larger than or equal to CounterLimit1
Counted value is larger than or equal to CounterLimit2
Counted value is larger than or equal to CounterLimit3
Counted value is larger than or equal to CounterLimit4
Counted value
Default
Description
Disabled
Operation Disable / Enable
Set
Select counting on positive and/or negative
sides
100
Value of the first limit
200
Value of the second limit
300
Value of the third limit
400
Value of the fourth limit
500
Maximum count value
Stop
Select if counter stops or rolls over after
reaching maxValue with steady or pulsed
overflow flag
0
Initial count value after reset of the function
Values (Range)
Unit
-
-
1MRK 506 335-UUS A
Description
Counted value
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents