Function Block - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 7
Current protection
7.2.3
7.2.4
7.2.5
Table 79:
SPTPIOC (50) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Pickup
5 - 2500
Table 80:
SPTPIOC (50) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
192

Function block

SPTPIOC (50)
I3P*
TRIP
BLOCK
TR_A
TR_B
TR_C
ANSI10000215-1-en.vsd
ANSI10000215 V1 EN
Figure 89:
SPTPIOC 50 function block
Signals
Table 77:
SPTPIOC (50) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
Table 78:
SPTPIOC (50) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
Settings
Unit
Step
-
-
%IB
1
Unit
Step
-
1
Default
Description
-
Three phase group signal for current inputs
0
Block of function
Description
Common trip signal
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
Default
Description
Disabled
Disable/Enable Operation
200
Phase current pickup in % of IBase
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 335-UUS A
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents