Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
6.1.5
Table 26:
ZQMPDIS (21) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CvtFltr
Disabled
Enabled
LineAng
0.00 - 90.00
KNMag
0.000 - 3.000
KNAng
-180 - 180
IMinPUPG
10 - 30
IMinPUPP
10 - 30
Table continues on next page
Technical manual
Table 25:
ZQMPDIS (21) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
TRZ1
BOOLEAN
TRZ2
BOOLEAN
TRZ3
BOOLEAN
TRZ4
BOOLEAN
TRZ5
BOOLEAN
PICKUP
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
PU_Z1
BOOLEAN
PU_Z2
BOOLEAN
Z3_PU
BOOLEAN
Z4_PU
BOOLEAN
Z5_PU
BOOLEAN

Settings

Unit
Step
-
-
-
-
Deg
0.01
-
0.001
Deg
1
%IB
1
%IB
1
Description
General trip
Trip signal for L1
Trip signal for L2
Trip signal for L3
Trip signal Zone1
Trip signal Zone2
Trip signal Zone3
Trip signal Zone4
Trip signal Zone5
Pickup
Start signal for L1
Start signal for L2
Start signal for L3
Start signal Zone1
Start signal Zone2
Start signal Zone3
Start signal Zone4
Start signal Zone5
Default
Description
Disabled
Disable/Enable Operation
Enabled
Enable CVT Filtering
80.00
Line impedance angle in degrees, common for
all zones
0.000
Common ground compensation factor
magnitude for Zone 2, 3, 4 & 5
-15
Common ground compensation factor angle
for Zone 2, 3, 4 & 5
15
Minimum operating phase current for phase to
ground loops, % of IBase
15
Minimum operating phase current for phase to
phase loops, in % of IBase
Section 6