Section 12
Scheme communication
12.1.7
12.2
12.2.1
12.2.2
502

Technical data

Table 336:
ZCPSCH (85) technical data
Function
Scheme type
Operate voltage, Delta V
Operate current, Delta I
Operate zero sequence voltage,
Delta 3V0
Operate zero sequence current,
Delta 3I0
Co-ordination time for blocking
communication scheme
Minimum duration of a carrier send
signal
Security timer for loss of guard signal
detection
Operation mode of unblocking logic
Current reversal and WEI logic for distance protection
3-phase ZCRWPSCH (85)
Identification
Function description
Current reversal and WEI logic for
distance protection 3-phase
Functionality
The current reversal function is used to prevent unwanted operations due to current
reversal when using permissive overreach or unblock protection or unblocking schemes
in application with parallel lines.
Range or value
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking
(0–100)% of VBase
(0–200)% of IBase
(0–100)% of VBase
(0–200)% of IBase
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
Disabled
NoRestart
Restart
IEC 61850
IEC 60617
identification
identification
ZCRWPSCH
1MRK 506 335-UUS A
Accuracy
-
± 5.0% of ΔV
± 5.0% of ΔI
± 10.0% of Δ3V0
± 10.0% of Δ3I0
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
-
ANSI/IEEE C37.2
device number
-
85
Technical manual