Simplified block diagram for ZMRPSB (68) function

Operating and inhibit conditions

Figure
85
presents a simplified logic diagram for the Power swing detection function
ZMRPSB (68).
The load encroachment characteristic can be switched off by setting the parameter
OperationLdCh = Disabled, but notice that the DFw and DRv will still be calculated from
RLdOutFw and RLdOutRv. The characteristic will in this case be only quadrilateral.
There are three different ways to form the internal INHIBIT signal:
Logical 1 on functional input BLOCK inhibits the output PICKUP signal
instantaneously.
The INHIBIT internal signal is activated, if the power swing has been detected and
the measured impedance remains within its operate characteristic for the time, which