Section 7
Current protection
Table 86:
OC4PTOC (51_67) Group settings (advanced)
Name
Values (Range)
HarmRestrain
Disabled
Enabled
2ndHarmStab
5 - 100
HarmRestrain1
Disabled
Enabled
HarmRestrain2
Disabled
Enabled
HarmRestrain3
Disabled
Enabled
HarmRestrain4
Disabled
Enabled
Table 87:
OC4PTOC (51_67) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
MeasType
DFT
RMS
7.3.6
7.3.7
198
Unit
Step
-
-
%IFund
1
-
-
-
-
-
-
-
-
Unit
Step
-
1
-
-

Monitored data

Table 88:
OC4PTOC (51_67) Monitored data
Name
Type
DIRL1
INTEGER
DIRL2
INTEGER
DIRL3
INTEGER
IL1
REAL
IL2
REAL
IL3
REAL
Operation principle
The protection design can be divided in four parts:
Default
Description
Disabled
Enable block from harmonic restrain
20
Pickup of second harm restraint in % of
Fundamental
Disabled
Enable block of step 1 from harmonic restrain
Disabled
Enable block of step 2 from harmonic restrain
Disabled
Enable block of step3 from harmonic restrain
Disabled
Enable block of step 4 from harmonic restrain
Default
Description
1
Selection of one of the Global Base Value
groups
DFT
Selection between DFT and RMS
measurement
Values (Range)
Unit
1=Forward
-
2=Reverse
0=No direction
1=Forward
-
2=Reverse
0=No direction
1=Forward
-
2=Reverse
0=No direction
-
A
-
A
-
A
1MRK 506 335-UUS A
Description
Direction for phase A
Direction for phase B
Direction for phase C
Current in phase A
Current in phase B
Current in phase C