Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 6
Impedance protection
124
BLOCK
NOT
startPhG
startPhPh
TimerSelZx
internalCommonStart
phSelStart
externalCommonStart
ANSI11000270 V3 EN
Figure 50:
Zone tripping logic
Timers separated - Separate start of timers within zone individually from phase to
ground and phase to phase measurement loops
Timers linked - Start of timers linked within zone, either phase to ground or phase to
phase will start both timers within zone
Internal start - Internal common start of timers from all the 5 zones
Start from PhSel - Common start of timers from phSelLogic Start signal, if direction
condition is forward for the particular phase and also the zone is set for DirModeZx
setting as Forward
External start - External common start of timers
Switch
:
Timers separated
FALSE
³1
Timers linked
Internal start
Start from PhSel
External start
1MRK 506 335-UUS A
operatePhG
tPEZx
&
³1
t
tPPZx
&
³1
t
operatePhPh
ANSI11000270-3-en.vsd
Technical manual