Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
14.15.5
Table 498:
SPVNZBAT Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
RtdBattVolt
20.00 - 250.00
BattVoltLowLim
60 - 140
BattVoltHiLim
60 - 140
tDelay
0.000 - 60.000
tReset
0.000 - 60.000
14.15.6
14.15.7
14.15.8
Technical manual

Settings

Unit
Step
-
-
V
1.00
%Vbat
1
%Vbat
1
s
0.001
s
0.001
Measured values
Table 499:
SPVNZBAT Measured values
Name
Type
V_BATT
REAL
BLOCK
BOOLEAN
Monitored Data
Table 500:
SPVNZBAT Monitored data
Name
Type
BATTVOLT
REAL
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are Enable and Disable.
The function execution requires that at least one of the function outputs is
connected in configuration.
The operation of the station battery supervision function can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.
Default
Description
Enabled
Disable/Enable Operation
110.00
Battery rated voltage
70
Lower limit for the battery terminal voltage
120
Upper limit for the battery terminal voltage
0.200
Delay time for alarm
0.000
Time delay for reset of alarm
Default
Description
0.00
Battery terminal voltage that has to be supervised
0
Blocks all the output signals of the function
Values (Range)
Unit
-
kV
Section 14
Monitoring
Description
Service value of the battery
terminal voltage
673