Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 6
Impedance protection
6.5.4
6.5.5
Table 51:
ZDNRDIR (21D) Group settings (basic)
Name
Values (Range)
AngNegRes
90 - 175
AngDir
5 - 45
IMinPUPG
5 - 30
IMinPUPP
5 - 30
Table 52:
ZDNRDIR (21D) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
166

Signals

Table 49:
ZDNRDIR (21D) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
Table 50:
ZDNRDIR (21D) Output signals
Name
Type
DIR_POL
GROUP SIGNAL
STDIRCND
INTEGER
Settings
Unit
Step
Deg
1
Deg
1
%IB
1
%IB
1
Unit
Step
-
1
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
Description
Polarizing voltage output for Mho
Binary coded directional information per measuring loop
Default
Description
115
Angle of blinder in second quadrant for forward
direction
15
Angle of blinder in fourth quadrant for forward
direction
5
Minimum pickup phase current for Phase-to-
ground loops
10
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Default
Description
1
Selection of one of the Global Base Value
groups
1MRK 506 335-UUS A
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading