Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
12.1.5
Table 333:
ZCPSCH (85) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SchemeType
Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking
tCoord
0.000 - 60.000
tSendMin
0.000 - 60.000
Table 334:
ZCPSCH (85) Group settings (advanced)
Name
Values (Range)
Unblock
Disabled
NoRestart
Restart
DeltaI
0 - 200
DeltaV
0 - 100
Delta3I0
0 - 200
Delta3V0
0 - 100
tSecurity
0.000 - 60.000
Table 335:
ZCPSCH (85) Non group settings (advanced)
Name
Values (Range)
GlobalBaseSelector
1 - 6
12.1.6
Technical manual

Settings

Unit
Step
-
-
-
-
s
0.001
s
0.001
Unit
Step
-
-
%IB
1
%VB
1
%IB
1
%VB
1
s
0.001
Unit
Step
-
1
Operation principle
Depending on whether a reverse or forward directed impedance zone is used to issue the
send signal, the communication schemes are divided into Blocking and Permissive
schemes, respectively.
A permissive scheme is inherently faster and has better security against false tripping than
a blocking scheme. On the other hand, a permissive scheme depends on a received signal
Scheme communication
Default
Description
Disabled
Disable/Enable Operation
Permissive UR
Scheme type
0.035
Communication scheme channel coordination
time
0.100
Minimum duration of a carrier send signal
(carrier continuation)
Default
Description
Disabled
Operation mode of unblocking logic
10
Current change level in % of IB for fault
inception detection
5
Voltage change level in % of UB for fault
inception detection
10
Zero seq current change level in % of IB
5
Zero seq voltage change level in % of UB
0.035
Security timer for loss of carrier guard detection
Default
Description
1
Selection of one of the Global Base Value
groups
Section 12
497