Monitored Data - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 7
Current protection
7.15.2.5
7.15.3
7.15.3.1
7.15.3.2
282

Monitored data

Table 168:
GOPPDOP (32) Monitored data
Name
Type
P
REAL
PPERCENT
REAL
Q
REAL
QPERCENT
REAL
Directional underpower protection GUPPDUP (37)
Identification
Function description
Directional underpower protection
Function block
GUPPDUP (37)
I3P*
TRIP
V3P*
TRIP1
BLOCK
TRIP2
BLK1
BFI_3P
BLK2
PICKUP1
PICKUP2
P
PPERCENT
Q
QPERCENT
ANSI08000507-1-en.vsd
ANSI08000507 V1 EN
Figure 133:
GUPPDUP (37) function block
Values (Range)
Unit
-
MW
-
%
-
MVAr
-
%
IEC 61850
IEC 60617
identification
identification
GUPPDUP
P <
2
SYMBOL-LL V2 EN
1MRK 506 335-UUS A
Description
Active Power
Active power in % of
calculated power base value
Reactive power
Reactive power in % of
calculated power base value
ANSI/IEEE C37.2
device number
37
Technical manual