Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
7.4.5
Table 92:
OC4SPTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
DirMode1
Disabled
Non-directional
Forward
Reverse
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
RI type
RD type
I1>
5 - 2500
t1
0.000 - 60.000
k1
0.05 - 999.00
IMin1
5 - 10000
t1Min
0.000 - 60.000
DirMode2
Disabled
Non-directional
Forward
Reverse
I2>
5 - 2500
t2
0.000 - 60.000
DirMode3
Disabled
Non-directional
Forward
Reverse
I3>
5 - 2500
t3
0.000 - 60.000
Table continues on next page
Technical manual

Settings

Unit
Step
-
-
-
-
-
-
%IB
1
s
0.001
-
0.01
%IB
1
s
0.001
-
-
%IB
1
s
0.001
-
-
%IB
1
s
0.001
Default
Description
Disabled
Operation Disable / Enable
Non-directional
Directional mode of step 1 off / non-directional /
forward / reverse
ANSI Def. Time
Selection of time delay curve type for step 1
1000
Phase current operate level for step1 in % of
IBase
0.000
Definite time delay of step 1
0.05
Time multiplier for the inverse time delay for
step 1
100
Minimum operate current for step1in% of IBase
0.000
Minimum operate time for inverse curves for
step 1
Non-directional
Directional mode of step 2 off / non-directional /
forward / reverse
500
Phase current operate level for step 2 in % of
IBase
0.400
Definite time delay of step 2
Non-directional
Directional mode of step 3 off / non-directional /
forward / reverse
250
Phase current operate level for step3 in % of
IBase
0.800
Definite time delay of step 3
Section 7
Current protection
207