Signals - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

1MRK 506 335-UUS A
6.6.4
6.6.5
Table 56:
PPLPHIZ Group settings (basic)
Name
Values (Range)
OperMode
No Filter
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
PU27PN
10.0 - 100.0
PU27PP
10.0 - 100.0
3V0PU
5.0 - 300.0
Pickup_N
10 - 200
tVN
0.000 - 60.000
tOffVN
0.000 - 60.000
tIN
0.000 - 60.000
Technical manual

Signals

Table 54:
PPLPHIZ Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
RELAG
BOOLEAN
RELBG
BOOLEAN
RELCG
BOOLEAN
PHSEL
INTEGER
Table 55:
PPLPHIZ Output signals
Name
Type
PICKUP
BOOLEAN
ZREL
INTEGER
Settings
Unit
Step
-
-
%VB
1.0
%VB
1.0
%VB
1.0
%IB
1
s
0.001
s
0.001
s
0.001
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Release condition for the A to ground loop
0
Release condition for the B to ground loop
0
Release condition for the C to ground loop
0
Integer coded external release signal
Description
Indicates start for ground fault(s), regardless of direction
Integer coded output release signal
Default
Description
No Filter
Operating mode (c=cyclic,a=acyclic)
70.0
Operate value of phase undervoltage in % of
VBase
50.0
Operate value of line to line undervoltage in %
of VBase
20.0
Operate value of residual voltage in % of
VBase
20
Operate value of residual current in % of IBase
0.100
Pickup delay for residual voltage
0.100
Dropoff delay for residual voltage
0.150
Pickup delay for residual current
Section 6
Impedance protection
171

Hide quick links:

Advertisement