Settings - ABB REL650 series Technical Manual

Line distance protection
Hide thumbs Also See for REL650 series:
Table of Contents

Advertisement

Section 6
Impedance protection
6.7.5
Table 62:
ZMRPSB (68) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
X1InFw
0.10 - 3000.00
R1LIn
0.10 - 1000.00
R1FInFw
0.10 - 1000.00
X1InRv
0.10 - 3000.00
R1FInRv
0.10 - 1000.00
OperationLdCh
Disabled
Enabled
RLdOutFw
0.10 - 3000.00
ArgLd
5 - 70
RLdOutRv
0.10 - 3000.00
kLdRFw
0.50 - 0.90
kLdRRv
0.50 - 0.90
IMinOpPE
5 - 30
176
Name
Type
BLKI01
BOOLEAN
BLKI02
BOOLEAN
I0CHECK
BOOLEAN
EXTERNAL
BOOLEAN
Table 61:
ZMRPSB (68) Output signals
Name
Type
START
BOOLEAN
ZOUT
BOOLEAN
ZIN
BOOLEAN

Settings

Unit
Step
-
-
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
-
-
ohm
0.01
Deg
1
ohm
0.01
Mult
0.01
Mult
0.01
%IB
1
Default
Description
0
Block inhibit of start output for slow swing condition
0
Block inhibit of start output for subsequent residual
current detect
0
Residual current (3I0) detection to inhibit start output
0
Input for external detection of power swing
Description
Power swing detected
Measured impedance within outer impedance boundary
Measured impedance within inner impedance boundary
Default
Description
Disabled
Disbled/Enabled operation
30.00
Inner reactive boundary, forward
30.00
Line resistance for inner characteristic angle
30.00
Fault resistance coverage to inner resistive
line, forward
30.00
Inner reactive boundary, reverse
30.00
Fault resistance line to inner resistive
boundary, reverse
Enabled
Operation of load discrimination characteristic
30.00
Outer resistive load boundary, forward
25
Load angle determining load impedance area
30.00
Outer resistive load boundary, reverse
0.75
Multiplication factor for inner resistive load
boundary, forward
0.75
Multiplication factor for inner resistive load
boundary, reverse
10
Minimum operate current in % of IBase
1MRK 506 335-UUS A
Technical manual